Generac's schedule runs on whichever limit you hit first — hours or time. Enter your current run hours and how long it has been since your last services, and this calculator works out which service level is due now and which is coming up next, using Generac's published schedule (shown in full, with its source, below the calculator).
Used for the one-time 25-hour break-in check.
Nothing is due yet on the figures you entered
Break-in: your unit has passed the 25-hour break-in point — make sure that first oil and oil filter change was done; it is a one-time item and is not tracked below.
Yearly maintenance
Not due yetInterval: every 100 hours or 12 months, whichever comes first. 20 hours and 2 months remain before this level is due.
Inspect for water intrusion; perform a fuel system leak test. (Daily checks — enclosure louvers, lines/connections for leaks, engine oil level — apply whenever the unit runs continuously or before each use.)
Schedule A
Not due yetInterval: every 200 hours or 24 months, whichever comes first. 120 hours and 14 months remain before this level is due.
Replace engine oil and oil filter; check battery condition, electrolyte level, and state of charge.
Schedule B
Not due yetInterval: every 400 hours or 48 months, whichever comes first. 320 hours and 38 months remain before this level is due.
Everything in Schedule A, plus: replace the engine air filter; clean and inspect the spark plugs (replace if necessary); inspect/adjust valve clearance where applicable — Next Generation units and Guardian 14/18 kW use hydraulic lifters and do not require the valve-clearance item.
Next up is Yearly maintenance, in 20 hours or 2 months, whichever comes first.
This is a planning aid based on Generac's published maintenance schedule — it names the service levels and intervals only, and is not a substitute for your owner's manual, which Generac says governs for your specific model. It does not provide service or repair procedures.
Generac's published schedule
Generac Next Generation Series 10-28 kW air-cooled and Generac Guardian Series 10-26 kW air-cooled (2017 to present), per Generac support. Generac states the table is an example/for reference — the model's owner's manual maintenance section governs.
| Task (as Generac names it) | Daily if running continuously or before each use | Every Year | Schedule A — every two years or 200 hours | Schedule B — every four years or 400 hours |
|---|---|---|---|---|
| Inspect enclosure louvers for dirt and debris * | ✓ | — | — | — |
| Inspect lines and connections for fuel or oil leaks | ✓ | — | — | — |
| Check engine oil level | ✓ | — | — | — |
| Inspect for water intrusion ** | — | ✓ | — | — |
| Perform fuel system leak test | — | ✓ | — | — |
| Check battery condition, electrolyte level, and state of charge | — | — | ✓ | — |
| Replace engine oil and oil filter † | — | — | ✓ | ✓ |
| Replace engine air filter | — | — | — | ✓ |
| Clean; inspect spark plug gap; replace if necessary | — | — | — | ✓ |
| Inspect/adjust valve clearance (where applicable) ‡ | — | — | — | ✓ |
| Inspect/clean sediment trap | — | See local codes and guidelines | — | — |
- Break-in / Schedule C: After the first 25 hours of run time (PowerPact 7.5 kW: first 20 hours). Change engine oil and oil filter after the break-in period. Units ship with conventional oil; do not switch to synthetic before break-in is reached. 'Schedule C' designation is used for Next Generation series.
- Yearly maintenance: Every 100 hours or every year, whichever comes first. Includes water-intrusion inspection and fuel system leak test (see yearly column).
- Schedule A: Every 200 hours or every two years, whichever comes first. Oil and oil filter replacement; battery condition/electrolyte/charge check.
- Schedule B: Every 400 hours or every four years, whichever comes first. Schedule A items plus air filter replacement, spark plug clean/gap-inspect/replace, valve clearance where applicable.
- Continuous use: Daily (every 24 hours of continuous running). Daily-column checks apply when running continuously or before each use.
- Extreme environments: generators operating below 40°F (<4.4°C) or above 85°F (>29.4°C) require an oil and oil filter change every year or after every 100 hours of run time since last service.
- ‡ Inspect/adjust valve clearance after the first 25 hours of run time (where applicable).
- Next Generation series generators and the 14 & 18 kW Guardian series generators use hydraulic lifters and therefore do NOT require a valve clearance inspection or adjustment.
- * / ** footnote markers appear in Generac's table as printed; their footnote text was not reproduced in the support article text read in this pass.